TECHNICAL SPECIFICATION :
PRODUCT DESCRIPTION
'SEMALARM 4002 & 6002' comes in modular construction based on a single micro controller chip, which is heart of the system. If lesser number of Windows/Channels are required, unwanted Window/Channels can be left blank. If higher number of Window/Channels are required, the modules can be stacked. Window display incorporates group of Super Bright LEDs. Fault legend inscription are provided on Film Negatives and Tracing Papers. Terminals are provided on back of the unit for connecting external Push Buttons and Hooter. Both NO/NC fault contacts can be selected on site. The sequence of operation listed below can also be selected on site. The healthiness of the unit is indicated with a watchdog LED indication.
The Modules consist of :-
a) Central Processing Unit.
b) Power Supply Unit.
c) Facia Display Unit.
d) Terminal Plate.
SEQUENCE OF OPERATION ( AS PER ISA S. 18.1 )
1) Manual Reset – M – ISA Ref. SEQUENCE – M
2)Auto Reset – A – ISA Ref. SEQUENCE – A
3) Ring Back – R – ISA Ref. SEQUENCE – R
4) First Out – F – ISA Ref. SEQUENCE – F2M-1
OPTIONAL FEATURES
Provision is available :-
- For Trip and Non -Trip Alarms. Display Windows are provided with different colour plastic / LEDs.
- For Trip and Non -Trip faults two Nos. outputs provided for Hooter.
(only M & A seq.)
- Extra Relay contact can be provided for repeat annunciation.
- Built in AC/DC fail annunciation.
- Vertical modules also available.
- Modules with Built in Push Buttons also available.
- Split architecture Version.
- RS 232 output.
ORDERING INFORMATION
- Model & Type No.
- Rated Supply Voltage
- Trip and Non-Trip facility required or not. – If required please specify
- Display Window in different colour.
- Discrimination through Audio device.
- Both.
- Built in AC or DC failure Annunciation facility required or not.
- Fault legend to be displayed. Please specify Tracing paper or Photo nagative.
- Type of Audio device used.
SEMUDA CORPORATION
INSTRUMENT DATA SHEET No. : TDAA/209
| TECHNICAL DATA OF ALARM ANNUNCIATOR |
|
SL.
No. |
Description |
Details |
|
1. |
MAKE |
SEMUDA |
|
2. |
MODEL No. |
SEMALARM 4002 & 6002 |
|
3. |
No. Of Window |
MODEL 4002 – 6,8 & 12
MODEL 6002 – 4,6,8,10,12,16,20 & 24,30,32,36,40
Multiples of Channel up to 96 Channel on request
Model 6002 only. |
|
4. |
Display Window Size |
MODEL 4002 : 45 X 45 m.m.
MODEL 6002 : 65 X 30 m.m. Or 30 X 30 mm. |
|
5. |
Type of Software |
Microprocessor based. |
|
6. |
Scane Time |
1 Micro sec. Approx. |
|
7. |
Power supply |
SMPS |
|
8. |
Rated Supply Voltage |
90 – 270V Universal / 22V – 60V Universal |
|
9. |
Power Consumption |
1.2 Watt < 6 VA / 2 Watt < 3 VA |
|
10. |
Rated Frequency |
50 / 60 Hz +/- 5% |
|
11. |
Interrogating Voltage |
+ 12V DC. |
|
12. |
Power Pack protection |
Over Load & Short Ckt. Protected |
|
13. |
Permissible Contact Resistance |
Less than or equal to 1.2 KW |
|
14. |
Contact Through Initiating |
6 Milli Amp. |
|
15. |
Display L.E.D. Rating |
10 Milli Amp. |
|
16. |
Flashing Rate |
60 / 30 per minute |
|
17. |
Insulation Resistance |
Infinity |
|
18. |
Nature of Alarm |
Potential Free |
|
19. |
Fault Input |
N / O or N / C Selectable for each window |
|
20. |
No. of L.E.Ds / Window |
5 Nos. Superbright L.E.D. |
|
21. |
L.E.D. Protection |
Through Resistance |
|
22. |
Response time of Flasher |
20 m.s. |
|
23. |
Alarm Sequence |
ISA Standard Sequence :
Manual Reset, Auto Reset, First Out & Ring Back. |
|
24. |
Enclosure Class |
Industrial. |
|
25. |
Relative humidity |
95% RH. |
|
26. |
Operating Temperature |
55 Dg. C. Maximm. |
|
27. |
Inscription |
On Tracing Paper or Photo Negatives. |
|
28. |
Material of PCB |
Glassepoxy |
|
29. |
Push Button details / Quantity |
N / O Contact. / 4 Nos. |
|
30. |
Colour of Window |
Red ( Green & Yellow on request ) |
|
31. |
Audio Contact Rating |
Potential Free N / O Contact,
Contact Rating 5Amp. @ 250V AC. / 28V DC resistive. |
|
32. |
Cascading Facility |
Provided |
|
33. |
Dielectric Test |
At 2 kV ac for 1 minute between Auxi. supply & body.
( CL. No. – 5 of IS : 3231 Pt. – 2, Sec. – 2 ) |
|
34. |
Impulse Test |
At 5 kV, 1.2mic.sec 3 positive & 3 nagative pulses between all
terminals & body. ( CL. No. – 5 of IS : 8686, 1977 ) |
|
35. |
Damped Oscillatory Wave Test
SAMEER – EMC Center - Mumbai
|
As per IEC 61000-4-12 Edition 1.1 2001-04 |
|
36. |
High voltage Test – At ERTL (E) |
2 kV between all terminals & earth for 1 minute |
|
37. |
Vibration Test – At ERTL (E) |
As per IS 9000 :- 3 Hrs. in all X, Y, & Z axis. |
|
38. |
Enviorment Test – At ERTL (E) |
As per IS 9000 :- a) Dry Heat Test - 85°C, 16 Hrs.
b) Damp Heat Test - 40°C, 48 Hrs., 95% RH.
c) Cold Test – 0°C, 4 hrs.
d) Performance Test – IR at 500V DC |
‘SEMUDA’ ALARM ANNUNCIATORS
DIMENSION DETAILS : Chart No. - DD / SEM / 0510
A. MODEL : SEMALARM 4002
| TYPE
NO. |
NO.OF
PTS.
|
BEZEL OUTSIDE |
PANEL CUTOUT |
DEPTH |
WINDOW
SIZE |
PUSH BUTTON |
| MC44512 |
12 |
220(W)x170(H)mm. |
203(W)x153(H)mm. |
140mm. |
45x45mm. |
NO |
| MC4458P |
8 |
220(W)x170(H)mm. |
203(W)x153(H)mm. |
140mm. |
45x45mm. |
YES |
| MC4456P |
6 |
220(W)x170(H)mm. |
203(W)x153(H)mm. |
140mm. |
45x45mm. |
YES |
B. MODEL : SEMALARM 6002
| TYPE
NO. |
No. OF
PTS. |
BEZEL OUTSIDE |
PANEL CUTOUT |
DEPTH |
WINDOW
SIZE |
PUSH
BUTTON |
| MCD1004 |
4 |
72(W)x144(H)mm. |
68(W)x138(H)mm. |
200mm. |
65x30mm. |
NO |
| MCD1P06 |
6 |
72(W)x144(H)mm. |
68(W)x138(H)mm. |
200mm. |
30x30mm. |
YES |
| MCD2006 |
6 |
144(W)x144(H)mm. |
138(W)x138(H)mm. |
200mm. |
65x30mm. |
NO |
| MCD2P06 |
6 |
144(W)x144(H)mm. |
138(W)x138(H)mm. |
200mm. |
65x30mm. |
YES |
| MCD2008 |
8 |
144(W)x144(H)mm. |
138(W)x138(H)mm. |
200mm. |
65x30mm. |
NO |
| MCD1008 |
8 |
72(W)x144(H)mm. |
68(W)x138(H)mm. |
200mm. |
30x30mm. |
NO |
| MCD3P10 |
10 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
65x30mm. |
YES |
| MCD3P11 |
11 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
65x30mm. |
YES |
| MCD3012 |
12 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
65x30mm. |
NO |
| MCD4P12 |
12 |
288(W)x144(H)mm. |
282(W)x138(H)mm. |
200mm. |
65x30mm. |
YES |
| MCD2P14 |
14 |
144(W)x144(H)mm. |
138(W)x138(H)mm. |
200mm. |
30x30mm. |
YES |
| MCD4P15 |
15 |
288(W)x144(H)mm. |
282(W)x138(H)mm. |
200mm. |
65x30mm. |
YES |
| MCD2016 |
16 |
144(W)x144(H)mm. |
138(W)x138(H)mm. |
200mm. |
30x30mm. |
NO |
| MCD4016 |
16 |
288(W)x144(H)mm. |
282(W)x138(H)mm. |
200mm. |
65x30mm. |
NO |
| MCD5P18 |
18 |
360(W)x144(H)mm. |
354(W)x138(H)mm. |
200mm. |
65x30mm. |
YES |
| MCD5020 |
20 |
360(W)x144(H)mm. |
354(W)x138(H)mm. |
200mm. |
65x30mm. |
NO |
| MCD3P22 |
22 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
30x30mm. |
YES |
| MCD3024 |
24 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
30x30mm. |
NO |
| MCD4P30 |
30 |
288(W)x144(H)mm. |
282(W)x138(H)mm. |
200mm. |
30x30mm. |
YES |
| MCD4032 |
32 |
288(W)x144(H)mm. |
282(W)x138(H)mm. |
200mm. |
30x30mm. |
NO |
| MCD5040 |
40 |
360(W)x144(H)mm. |
354(W)x138(H)mm. |
200mm. |
30x30mm. |
NO |
Combination of Big & Small Window. (Big = 65X30mm.) & (Small = 30X30mm.) |
| MCD1P04 |
4 |
72(W)x144(H)mm. |
68(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD2P08 |
8 |
144(W)x144(H)mm. |
138(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD2P10 |
10 |
144(W)x144(H)mm. |
138(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD2P12 |
12 |
144(W)x144(H)mm. |
138(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD3P12 |
12 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD3P15 |
15 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD4P16 |
16 |
288(W)x144(H)mm. |
282(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD3P18 |
18 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD5P20 |
20 |
360(W)x144(H)mm. |
354(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD3020 |
20 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
Combined. |
NO |
| MCD3P20 |
20 |
216(W)x144(H)mm. |
210(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD5P32 |
32 |
360(W)x144(H)mm. |
354(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD5P35 |
35 |
360(W)x144(H)mm. |
354(W)x138(H)mm. |
200mm. |
Combined. |
YES |
| MCD5036 |
36 |
360(W)x144(H)mm. |
354(W)x138(H)mm. |
200mm. |
Combined. |
NO |
| MCD5P36 |
36 |
360(W)x144(H)mm. |
354(W)x138(H)mm. |
200mm. |
Combined. |
YES |
NOTE : Cascading facility provider up ta 20 Pt. Units.
C. MODEL : DS DISPLAY FACIA
| TYPE
NO. |
NO.OF
PTS. |
BEZEL OUTSIDE |
PANEL CUTOUT |
DEPTH |
WINDOW SIZE |
| DS6PC4 |
4 |
72(W) x 144(H)mm. |
68(W) x 138(H)mm. |
65mm. |
65 x 30 mm. |
| DS6PF4 |
4 |
72(W) x 144(H)mm. |
68(W) x 138(H)mm. |
200 mm |
65 x 30 mm. |
| DS6PC8 |
8 |
72(W) x 144(H)mm. |
68(W) x 138(H)mm. |
65 mm. |
30 x 30 mm. |
| DS6PF8 |
8 |
72(W) x 144(H)mm. |
68(W) x 138(H)mm. |
200 mm, |
30 x 30 mm. |
OPEARATING INSTRUCTION MANUAL
Chart No. : OM1 / 208 / 10
‘SEMUDA’ Microprocrssor Based Audio Visual Alarm Annunciators.
Model : SEMALARM 6002 & SEMALARM 4002.
Apply rated supply voltage between L & N
Connect potential free input contacts N/O or N/C
Press. :- 1) Test Push Button – All Windows Flash & Audio ON
2) Silent Push Button – All Windows Flash & Audio OFF
3) Ack Push Button – All Windows Steady & Audio OFF
4) Reset Push Button – All Windows OFF & Audio OFF
For Replacing Legend :-
Remove window frame & insert required legend betweens 2 plastic Sheets.
How to stack multiple Annunciator Units :-
Connect Parallely Test, Silent, Ack & Reset Push Buttons, Hootet A & B audio terminals
|